Wire Gauge Amp Capacity Lookup
Methodology, scope, and sources
Ampacity and resistance values come from Southwire product engineering data for copper XHHW-2, copper THHN/THWN-2, and aluminum XHHW-2 conductors. Southwire identifies the ampacity conditions as based on the 2023 NEC Table 310.16: insulated conductors in raceway, cable, or earth, no more than three current-carrying conductors, and 30°C ambient. The small-copper specification was updated April 22, 2026; the linked aluminum specification was updated January 7, 2026. The 60°C entries were cross-checked against Southwire’s published copper and aluminum 60/75/90°C engineering tables. NumPad does not reproduce an NEC table.
Temperature-column limitation. Equipment markings govern the usable termination temperature. UL’s public guides explain that a higher insulation temperature rating alone does not permit using a higher ampacity at a lower-rated terminal. See the UL Panelboards Guide, UL Circuit Breaker Guide, and UL Wire and Cable Guide.
Voltage drop. The calculator uses the manufacturer’s DC resistance at 25°C and the formulas shown in the calculator. The 3%/5% design guidance is described in NEC informational notes; it is not presented here as a universal mandatory threshold. See NFPA’s public 2025 NEC development materials.
Jurisdiction. NEC edition adoption and local amendments vary. Verify the adopted rules with the authority having jurisdiction; NFPA’s NEC enforcement maps provide general adoption context.
Primary data sources: 14–10 AWG copper, 8 AWG–500 kcmil copper, and 8 AWG–500 kcmil aluminum. Last verified: August 27, 2026.
How to use this reference
Start with the installation, not only the gauge. Identify the conductor or cable type, material, equipment temperature markings, ambient conditions, current-carrying conductor count, and applicable code edition before choosing a reference column.
Keep ampacity and overcurrent protection separate. A tabular ampacity is one input to a circuit design. Load calculations, small-conductor rules, continuous or nonlinear loads, motors, appliances, services, feeders, and listed equipment can introduce other requirements or exceptions.
Treat voltage drop as a planning estimate. It can help compare conductors under the same simplified assumptions, but it does not replace an engineering calculation for sensitive, long, large, or complex AC circuits.
Have a qualified electrician or engineer complete and verify the final design, and confirm it with the authority having jurisdiction.